GDWS-311RC SF6 Gas Dew Point Tester

GDWS-311RC SF6 Gas Dew Point Tester

Brief Description:

GDWS-311RC is ideal instrument when it is necessary to test water content of SF6 gas. The core component is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument

 


Product Detail

Product Tags

SF6 Gas Dew Point Tester GDWS-311RC
General Information

GDWS-311RC is ideal instrument to test dew point of SF6 gas. The core component is DRYCAP series sensors produced by Finland Vaisala company. With professional hardware chips and excellent software algorithms of STMicroelectronics, we have produced a new generation of gas moisture test instrument.

Application

Moisture monitoring of SF6 gas electrical equipment for electric power
SF6 gas cylinder gas quality test
High purity gas manufacturing
Semiconductor industry dry gas supply
Research and development use
Clean room/dry house monitoring
Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.

Features

Better than ±2℃ measurement accuracy.
All gas path are polymer material design, ensures no water wall hanging phenomenon and guarantees the test speed.
The oil-free stainless steel body regulating valve is used to ensure the accuracy of the measured value.
Advanced software algorithms improve the test accuracy of sensors.
Combined chassis configuration solution, users can easily combine related instruments and accessories. The overall package is carried, which makes the user have a more relaxed experience.
Start up test, no need to preheat and oscillate.
Temperature conversion and pressure data correction.
Fuzzy computing technology.
High-power lithium battery power, realize AC and DC dual power supply. No on-site AC power is required. Lithium battery power supply continues to work for more than 8 hours without the need of an external power supply.
Anti-electromagnetic interference circuit design to ensure product reliability.
Gas recycling function, environment-friendly.
The test data is stable and can provide both standard dew point values and converted dew point values at 20℃.
The best test flow area shows that the user can adjust the gas flow intuitively and quickly. Reduce test time.
The air inlet is designed with a miniature self-sealing joint, and the air path to be tested will not leak when the air path is disconnected.

Specification

Measurement method: Resistive and Capacitive measurement principle
Measurement range: dew point -80℃--+20℃(support ppmv)
Accuracy: ±2℃
(when the dew point temperature is below 0℃, the sensor output is the frost point)
Response time: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
Resolution: 0.01℃
Repeat-ability: ± 0.5℃
Display unit: ℃, ppm, ℃P20(converted value at 20℃)
Gas flow: 400-600ml/min
Flow display: 0-1000mL digital flow meter
Sample gas pressure: ≤1MPa
Power supply: 220VAC±10%, 50Hz, AC/DC use, continuous working is not less than 8 hours.
Use environment temperature: -20--+60℃
Environment humidity: 90%RH
Measurement value influence: No affect of pressure and flow
Dimension: 395*295*155mm
Weight: about 2kg

Accessories
Main unit 1 piece
Adapter 1 set
Teflon pipe(include flow adjustment valve and fast connector) 1 set
Tail pipe 1 set
Spare parts 1 set
Charger 1 piece
Users Guide 1 copy
Test Report 1 copy